High-performance computing data centre, Sochi
Reconstruction of a building into a data centre for high-performance computing. We lead it from the concept and functional requirements to a roadmap under GOST R 58811-2020.
What’s done
- Concept and layout
- Functional requirements for design
- Pre-design brief, seven stages
- Load balance across seven emergency modes
- Roadmap under GOST R 58811-2020 and a participant matrix
- Reliability
- Tier III
- Power
- 6.5 MW first stage, sketch up to 15 MW
- Racks
- 107 server racks up to 35 kW, 25 network racks up to 20 kW
- PUE
- no more than 1.5, design 1.4
- Redundancy
- 10 kV — 2N, 0.4 kV — 2N+1, fuel 24 h
- Commissioning
- three stages, two independent locations
Data-centre brief: 17 findings before expert review
A client’s set went through the requirements check. The review is rule-based — no language-model calls, the result reproduces word for word. The full report is open without sign-up.
Metodium school runs its students in tm.educ
An educational ecosystem for children and parents from Saint Petersburg. The school website, sign-up, payments and lesson records run on our service — the school works with children, not spreadsheets.
What’s done
- metodium.ru website with programmes, courses and sign-up
- Admin workspace: monthly lesson grid, debts, teacher payouts
- Teacher calendar with reschedule requests
- Parent workspace: next lesson, video call, payment history and receipts
- Bot with lesson and payment reminders
- Online course payments with receipts
Pre-design calculation for a 6 MW AI data centre
The first phase is mixed: colocation sells from day one, the AI zone grows in blocks for a confirmed customer. The client is not disclosed.
What the calculation showed
- Energy balance with battery recharge and a check for degraded EER
- Three risks before design: density growth, cluster power spikes, redundancy on a hot day
- Composition
- 236 rack spaces, 4,052 kW IT within a 6 MW limit
- Density
- 7 to 140 kW per rack
- UPS
- 9,600 → 7,500 kW at the same load
- Batteries
- 2,400 → 1,450 kWh, N+1 for the AI loop, 2N for the core
A construction company’s money map: 22,729,840 ₽
This is what diagnostics delivers. The demo company StroyGrad on a standard 1C: the company is fictional, the calculation is real — the same reports the service builds on your database.
Team experience
Before tm.hub
Kirill Sokolov and Stanislav Falaleev — data-centre operation and construction, power supply, a federal operator’s networks.
Operating a federal transport network with 99.9%+ availability, 24×7 emergency management, communication nodes, server rooms and mini-DCs.
Construction commission for a 20 MW data centre: inputs and brief, control of power sections, finding mismatches between works and drawings, lab tests and as-built documents for commissioning.
Upgrading 0.4 kV switchgear, guaranteed power and batteries at sites in Moscow, Novosibirsk and Perm; incident analysis and fewer points of failure.
Campus engineering and IT systems, OPEX and contractors, building and equipping research spaces including an IT and AI centre.
Review of briefs, design and working documentation, comments to the general designer, as-built documents and acceptance.
Shifts and SOP, MOP and EOP procedures, maintenance and spares, incident management, SLA and failure analysis.